  • Which instrument should be used to perform a dielectric watt loss test?

    The core instrument used for dielectric loss testing (loss tangent tanδ measurement) is a Dielectric Loss Test Set, also known as a Tan Delta Tester or Schering Bridge. Based on technical principles and automation levels, the main types are:


    205


    1. Traditional Schering Bridge


    Principle: Classic balanced bridge method requiring manual adjustment of resistive/capacitive arms to achieve balance for calculating tanδ and capacitance.


    Characteristics:

    High accuracy (historically the laboratory standard).

    Complex operation, demanding skilled personnel.

    Slow testing speed.

    Requires external HV source (e.g., test transformer) and reference capacitor.


    Application: Laboratory precision measurements or calibration reference. Rarely used for field preventative testing today.


    2. Digital Automatic Dielectric Loss Testers


    Principle: Uses digital measurement techniques (e.g., digital sampling, vector analysis) to automatically measure current magnitude/phase difference under applied voltage. Directly calculates and displays tanδ, capacitance (Cx), power factor (PF), leakage current, etc. Typically integrates HV source and measurement unit.


    Characteristics:

    Industry Standard: The dominant choice for field and factory testing.

    Automated: Simple operation (one-button testing), automatic calculation/display, no manual balancing.

    Fast & Efficient: High testing speed.

    Integrated: Usually contains built-in HV source (outputting AC test voltages like 10kV or higher) and reference measurement unit. Portable (though larger capacity units may be heavier).

    Versatile: Tests various equipment (transformer windings-windings/ground, bushings, CTs/VTs, cables, capacitors). Supports multiple test modes (Direct/Standard, Reverse, GST/GST-Guard).

    Strong Anti-Interference: Features digital filtering and noise suppression.

    Data Management: Stores results; some models offer Bluetooth/USB transfer or printing.


    Test Modes:

    Direct/Standard Mode: HV applied to test object's HV terminal (e.g., transformer HV winding), measurement terminal connected to LV terminal (or ground screen). For objects with one end grounded (e.g., transformer windings).

    Reverse Mode: HV applied to HV terminal, measurement terminal floated; instrument chassis (ground) connected to test object's LV terminal. For objects with neither end grounded (e.g., capacitive bushing tap).

    GST/Guard Mode: Uses the test object itself as a voltage source (primarily for CVT measurements).


    3. Variable Frequency Dielectric Loss Testers (VFDS / VLF)


    Principle: Extends digital automatic testers with variable frequency capability (typically adjustable between 15Hz - 400Hz+).


    Characteristics & Advantages:

    Key Advantage: Superior Anti-Interference: Field environments often have strong 50/60Hz power frequency noise. VFDS shifts test frequency away from interference (mains frequency & harmonics), drastically improving signal-to-noise ratio for more accurate/reliable tanδ results, especially in noisy substations.

    Retains all benefits of digital automatic testers (automation, integration, versatility).


    Application: Essential for precise measurements in high-interference field environments (e.g., live substations, testing near energized equipment). The preferred high-end choice for modern field testing.

    നിങ്ങൾക്ക് ഇതുകൂടി ഇഷ്ടപ്പെട്ടേക്കാം

    • എന്തെങ്കിലും ചോദ്യങ്ങളുണ്ടോ!

      ഏത് സമയത്തും ഞങ്ങളെ ബന്ധപ്പെടാൻ മടിക്കരുത്
      ഞങ്ങളെ സമീപിക്കുക
    • ഞങ്ങളെ സന്ദർശിക്കുക

      ബിൽഡിംഗ് 6, ഒപ്റ്റിക്‌സ് വാലി ഒപ്റ്റിക്കൽ-മെക്കാനിക്കൽ ഇൻഡസ്ട്രിയൽ പാർക്ക്, 84 ഗാക്‌സിൻ 5 റോഡ്,
      ഈസ്റ്റ് ലേക്ക് ന്യൂ ടെക്‌നോളജി ഡെവലപ്‌മെന്റ് സോൺ, വുഹാൻ സിറ്റി, ഹുബെയ് പ്രവിശ്യ, ചൈന

    • ഞങ്ങൾക്ക് ഇമെയിൽ ചെയ്യുക

      qiao@hvtest.cc

    • ഞങ്ങളെ വിളിക്കൂ

      +86-15871365102