qiao@hvtest.cc15871365102
  • What factors can affect the test results of the grounding resistance tester

    The grounding resistance tester under UHV power can help many power workers conduct various power tests more conveniently.

    8

    The grounding resistance tester is used to measure the grounding resistance values of various equipment such as power, communication, lightning protection, iron towers, electromechanical, broadcasting and television, buildings, troops, laboratories, workshops, water affairs, large factories, railways, and industries. And departments such as mining enterprises.

    1) The soil composition around the grounding system (ground grid) is inconsistent, the geology is different, the tightness and dryness are different, and it is dispersed. There are stray currents on the surface, especially overhead ground wires, underground water pipes, cable sheaths, etc. The impact of testing is particularly significant. The solution is to measure at different points and take the average.

    2) The direction of the test line is incorrect and the distance is not long enough. The solution is to find the testing direction and distance.

    3) The resistance of the auxiliary grounding electrode is too high. The solution is to splash water on the grounding pile or use a reducing agent to lower the grounding resistance of the current electrode.

    4) The contact resistance between the test clip and the grounding measurement point is too high. The solution is to use a file or sandpaper to polish the contact points, and use a probe clip to completely clamp the polished contact points.

    5) Interference effect. The solution is to adjust the pay off direction, avoiding directions with significant interference as much as possible, and reducing meter reading fluctuations.

    6) Instrument usage issues. The battery level is low, the solution is to replace the battery. The accuracy of the instrument has decreased, and the solution is to recalibrate it to zero.

    Therefore, it is necessary to understand the factors that may affect the detection results of the grounding resistance detector in different usage environments.

    നിങ്ങൾക്ക് ഇതുകൂടി ഇഷ്ടപ്പെട്ടേക്കാം

    • എന്തെങ്കിലും ചോദ്യങ്ങളുണ്ടോ!

      ഏത് സമയത്തും ഞങ്ങളെ ബന്ധപ്പെടാൻ മടിക്കരുത്
      ഞങ്ങളെ സമീപിക്കുക
    • ഞങ്ങളെ സന്ദർശിക്കുക

      ബിൽഡിംഗ് 6, ഒപ്റ്റിക്‌സ് വാലി ഒപ്റ്റിക്കൽ-മെക്കാനിക്കൽ ഇൻഡസ്ട്രിയൽ പാർക്ക്, 84 ഗാക്‌സിൻ 5 റോഡ്,
      ഈസ്റ്റ് ലേക്ക് ന്യൂ ടെക്‌നോളജി ഡെവലപ്‌മെന്റ് സോൺ, വുഹാൻ സിറ്റി, ഹുബെയ് പ്രവിശ്യ, ചൈന

    • ഞങ്ങൾക്ക് ഇമെയിൽ ചെയ്യുക

      qiao@hvtest.cc

    • ഞങ്ങളെ വിളിക്കൂ

      +86-15871365102