  • Five points to note in microcomputer relay AC test

    The relay protection tester under UHV power can help many power workers conduct various power tests more conveniently.

    HTY_4644

    The issues that power workers need to pay attention to when using microprocessor relay protection testers for AC testing are summarized as follows:

    1. One of the general testing steps for relay protectors is to set the "switch positioning confirmation time". We need to pay attention to setting it larger here, such as around 20ms. If there is a significant error in the test return value, it may be due to the large shaking of the relay contacts. In this case, the test can continue in "manual" mode. To ensure reliable operation of relay protection, it is necessary to ensure that the output of the tester is greater than the starting value of the protection when detecting the relay action time.

    2. The conventional method for detecting multi-stage overcurrent protection is to test separately in a section and gradually increase the current until the protection is activated. However, the action time detected through this traditional method is often inaccurate. When detecting the action time at this time, pay attention to directly outputting a positive action value of 1.2 times or more from the tester. At this point, the low voltage protection becomes less than 0.8 times, ensuring the activation of the protection and therefore the measured action time is more accurate.

    3. The detection of distance protection requires attention to the conventional setting value of 0.95 times for detection. At this time, the short-circuit impedance is less than the set value to ensure reliable protection and exit. When simulating grounding distance faults, it is also important to pay attention to the correct setting of the zero sequence compensation coefficient.

    4. When checking the zero sequence current, it is necessary to distinguish whether the fixed value given in the value table is 3I0 or I0. If customized as I0, display the bottom left corner of the detection module; If customized as 3I0, the value in the bottom left corner will be multiplied by 3 to see if it matches that value.

    5. For the detection of low cycle protection, the selection frequency can be changed. The frequency change step size of "automatic mode" is better than that of manual mode. Manual mode is difficult to control because df/dt is locked at a low cycle value. The step size of frequency variation is set according to the accuracy requirements. The frequency has decreased from 50 to provide protection. It should be noted that the interval time is longer than the protection action time.

    These are five points to note when conducting AC testing on microprocessor relay protection testers.

    നിങ്ങൾക്ക് ഇതുകൂടി ഇഷ്ടപ്പെട്ടേക്കാം

    • എന്തെങ്കിലും ചോദ്യങ്ങളുണ്ടോ!

      ഏത് സമയത്തും ഞങ്ങളെ ബന്ധപ്പെടാൻ മടിക്കരുത്
      ഞങ്ങളെ സമീപിക്കുക
    • ഞങ്ങളെ സന്ദർശിക്കുക

      ബിൽഡിംഗ് 6, ഒപ്റ്റിക്‌സ് വാലി ഒപ്റ്റിക്കൽ-മെക്കാനിക്കൽ ഇൻഡസ്ട്രിയൽ പാർക്ക്, 84 ഗാക്‌സിൻ 5 റോഡ്,
      ഈസ്റ്റ് ലേക്ക് ന്യൂ ടെക്‌നോളജി ഡെവലപ്‌മെന്റ് സോൺ, വുഹാൻ സിറ്റി, ഹുബെയ് പ്രവിശ്യ, ചൈന

    • ഞങ്ങൾക്ക് ഇമെയിൽ ചെയ്യുക

      qiao@hvtest.cc

    • ഞങ്ങളെ വിളിക്കൂ

      +86-15871365102